I Receive Error -301096 (Timeout) When Uploading or Downloading Calibration Data to My ECU Using ECUMC Toolkit Examples

Updated Oct 27, 2026

Issue Details

When I use ECUMC toolkit examples such as Edit a Characteristic.vi or Measurement and Calibration Application.vi to connect to my ECU, I receive the error shown below. In some cases, the ECU may also behave abnormally. However, third-party software can access the ECU successfully, and I have verified that the .a2l file is correct. How can I resolve this issue?


error.png

Solution

This issue is commonly caused by the ECU's default Calibration Page configuration preventing access from the host. The ECUMC toolkit examples may not be configured to use the correct Calibration Page.
 
To resolve this issue:
  1. Verify the available Calibration Pages using A2L Viewer or another XCP database tool.

A2l viewer.png

  1. Open the Edit a Characteristic.vi example and add or configure the Set Calibration Page operation in the code.

Customized Example.png

  1. Run the modified VI.