Error When Downgrading Real-Time PXI Controller Software

Updated May 3, 2018

Reported In

Hardware

  • PXIe-8840
  • PXIe-8820

Software

  • LabVIEW 2014 SP1 Full
  • LabVIEW 2015 Full
  • LabVIEW 2014 Full
  • LabVIEW 2014 Professional
  • LabVIEW 2014 SP1 Professional
  • LabVIEW 2015 Professional

Issue Details

I have a PXI Real-Time Controller that I'd like to downgrade the software on from 2014 SP1 or higher to 2014. I also have LabVIEW 2014 SP1 and 2015 installed on my normal host machine, and I'm using that computer to downgrade the software. I'm working with a customer who needs to use older software, or my application requires me to go back a version in software. When I try to downgrade to 2014, I receive the following error:

Cannot continue because of the following unresolved dependencies : 
NI RT Extensions for SMP (MultiCore Support) 14.0.0 requires Base System 11.0


How do I resolve this error?

Solution

There are a few options to work around this error.
  • Try installing software on the chassis from a different computer. 
  • Uninstall only NI RT Extensions for SMP (MultiCore Support) 14.5.0 version, then downgrade the remaining software on the target to 14.0. 
    • Then, install only NI RT Extensions for SMP (MultiCore Support) 14.0.0 on the target.
  • Downgrade all of the components, except for NI RT Extensions for SMP (MultiCore Support). Then downgrade just the NI RT Extensions for SMP (MultiCore Support).