cRIO 903x Set to Force Safe Mode After Deploying Image with Replication and Deployment (RAD) Utility

Updated May 11, 2018

Reported In

Hardware

  • cRIO-9031

Issue Details

When I deploy an image using RAD to the cRIO-9031 controller, it always goes into forced safe mode. What can I do to make sure that this doesn't happen in the future?

Solution

This was actually a bug in older versions of the RAD Utility that affected cRIO-903x targets. This issue was resolved in RAD Version 16.0.0, so upgrading to 16.0.0 should resolve the behavior. Please reference the changelog in the Replication and Deployment Utility page for more information about what was changed in RAD Version 16.0.0